INDICES OF PROTECTION FOR THE VARIOUS TYPES OF BUILDINGS
The indices of protection IP and code IK indicated in the form below are given by guide UTE C 15-103. For certain buildings located by *, guide UTE C 15-103 indicates higher IP and IK for unusual condition of uses.
Concept IP or International Protection, meets the standard on the safety of the electronic components and the people not having to have access to the hot or dangerous elements while running high.
The first figure characterizes the solid bodies and the second, the liquid bodies. Just as there will exist concepts of angles or tools, material or zones on the person.
If the first or the second figure does not require obligation, then information will be carried with X or XX, example IPX2 to navoir only one protection with rainwater with a slope with 15°
Concept IK is a group of figures which characterizes an energy value or impact on materials having for function to protect equipment often external and submitted to some excited people at exit from stage or nightclub.
So as to meet the ISO standards on the anti-effraction or of high security, the elements must answer the note the highest IK10, that is to say 20 joules
or a force X outdistances, with a force corresponding to a mass X the acceleration of weightlessness:
To obtain 20 joules: A ball dacier of 4kg X 9,81 = 39,24 NR X 0,50 m ⇒ approximately 20 joules.
To meet the standard, the test must qualify the object by repeating 5 rebounds at various places or 3 rebounds at only one place and preferably in the center.

1-figure: protection against the solid bodies 2-figure: protection against the liquids
IP   IP  
0 no protection 0 no protection
1 protected against the bodies
solids superior has 50 mm
1 protected against the falls
vertical of water tastes
2 protected against the bodies
solids superior has 12 mm
2 protected against the falls from
taste water has 15° the vertical one
3 protected against the bodies
solids superior has 2.5 mm
3 protected against the falls from
taste water has 60° the vertical one
4 protected against the bodies
solids superior has 1 mm
4 protected against water projections
of any directions
5 protected against dust 5 protected against water projections
of any directions to the lance
6 completely protected against dust 6 protected against projections
comparable to the big waves
    7 protected against the effects of immersions
    8 protected against the effects of immersions
prolonged under specified conditions

IK energy of shock
00 not protected
01 0,15 joules
02 0,20 joules
03 0,35 joules
04 0,50 joules
05 0,70 joules
06 1 joules
07 2 joules
08 5 joules
09 10 joules
10 20 joules

additional letter, designation
With protected against the access from the back of the hand
B protected against the access from the finger
C protected against the access from a tool of 0.25 mm
D protected against the access from a tool of 1 mm
H material with high pressure
M movement during tests with water
S stationary during tests with water
W bad weather

Buildings or sites:
Domestic buildings
IP ⁄ IK
Technical premises:
IP ⁄ IK
Additional boiler rooms and buildings:
IP ⁄ IK
Garages and car parks higher than 100 m2:
IP ⁄ IK
Medical buildings of collective use:
IP ⁄ IK
Buildings of collective use:
IP ⁄ IK
Buildings or sites in a farm:
IP ⁄ IK
various installations:
IP ⁄ IK
Industrial plants:
IP ⁄ IK
Industrial plants:
The installations must answer the general terms of the safety regulations
applicable to these establishments (article EL)
IP ⁄ IK

execution time customer :
runtime server : 0.028 seconds